Johnson Controls Temperature Control with Display and Sensor, Electronic, Series: A419, 120 - 240 VAC, 16 amp at 120 VAC, 8 amp at 240 VAC Full Load, A99BB Type PTC Sensor, SPDT, Open/Close on Rise Switching Action, 6.5 feet Capillary Length, 50/60 Hz, 15 amp, 1 hp (NO)/10 amp 0.25 hp (NC) at 120 VAC Non-Inductive, 16 amp, 1 hp (NO)/5.8 amp, 0.25 hp (NC) Full Load at 120 VAC, 96 amp, 1 hp (NO)/34.8 amp, 0.25 hp (NC) Locked Rotor at 120 AVC Contact, Digital, 1 Switch, 1 - 30 deg F Differential, -30 to 212 deg F Setting Temperature, -26 to 140 deg F, Gray, 2-1/2 Inch Width x 5 Inch Height x 2-1/2 Inch Depth, NEMA 1
Amperage Rating ?????
|
16 amp at 120 VAC, 8 amp at 240 VAC Full Load
|
Brand Name ?????
|
Johnson Controls
|
Capillary Length ?????
|
6.5 feet
|
Color ?????
|
Gray
|
Configuration ?????
|
SPDT
|
Contact Rating ?????
|
15 amp, 1 hp (NO)/10 amp 0.25 hp (NC) at 120 VAC Non-Inductive, 16 amp, 1 hp (NO)/5.8 amp, 0.25 hp (NC) Full Load at 120 VAC, 96 amp, 1 hp (NO)/34.8 amp, 0.25 hp (NC) Locked Rotor at 120 AVC
|
Differential Temperature ?????
|
1 - 30 deg F
|
Dimensions ?????
|
2-1/2 Inch Width x 5 Inch Height x 2-1/2 Inch Depth
|
Dimension ?????
|
2-1/2 Inch Width x 5 Inch Height x 2-1/2 Inch Depth
|
Display Type ?????
|
Digital
|
Enclosure Type ?????
|
NEMA 1
|
Enclosure ?????
|
NEMA 1
|
Frequency Rating ?????
|
50/60 Hz
|
Item Name ?????
|
Temperature Control with Display and Sensor
|
Number of Switches ?????
|
1
|
Sensor Type ?????
|
A99BB Type PTC
|
Series ?????
|
A419
|
Setting Temperature ?????
|
-30 to 212 deg F
|
Sub Brand ?????
|
Penn
|
Switching Action ?????
|
Open/Close on Rise
|
Temperature Rating ?????
|
-26 to 140 deg F
|
Type ?????
|
Electronic
|
Voltage Rating ?????
|
120 - 240 VAC
|
- Easy to read front panel LCD displays sense the temperature and control function status clearly, custom icons on the display indicate the control and system status at a glance
- Wide temperature differential adjustment range allows the user to set a precise 1 deg F temperature differential from 1 - 30 deg F providing a much tighter differential than electromechanical controls
- Adjustable anti-short cycle delay 0 - 12 min in 1 min increments ensures that the output relay remains off for a user set time delay, which helps avoid hard starts, nuisance overload outages and unnecessary equipment wear
- Switch activated temperature offset function allows the user to shift the cut-in and cut-out setpoints by and adjustable offset based on the status of a user installed, external switch, such as a time clock
- High impact, thermoplastic enclosures increase application options, allowing surface and snap-fit DIN rail mount
- Lockable front panel touchpad allows easy set up and adjustment of the A419 control setpoint, differential and other functions, a concealed jumper locks the touchpad and deters unauthorized adjustment of the control settings
- 1.8 VA maximum power consumption